Nominal quvvat: 200kVA
Nominal kuchlanish: 11/6.6-0.4kV
Nominal oqim: 10,5/17,5/288,68A
Nominal chastota: 50Hz
Ulanish belgisi: Dyn11

Xususiyatlari

1.Mahsulot spetsifikatsiyasi

Nominal quvvat: 200kVA

Nominal kuchlanish: 11/6.6-0.4kV

Nominal oqim: 10,5/17,5/288,68A

Nominal chastota: 50Hz

Fazalar soni: 3 faza

Ulanish belgisi: Dyn11

Sovutish usuli: ONAN

Izolyatsiya sinfi: A

Izolyatsiya darajasi: LI 75 AC28 / LI AC3

200 kva 11kv 6.6kv 0.4kv dual voltage distribution transformer 6

2. Sinov standarti:

IEC 60076

3. Test elementi

3.1Voltaj nisbati o'lchovi va ulanish guruhi testi

HV1 o'rash

LV o'rash

Nominal nisbat

Voltaj og'ish foizi

Ulanish belgisi

Joyga teging

Kuchlanishi

(V)

Kuchlanishi

(V)

AB% 2fab

Miloddan avvalgi / miloddan avvalgi

CA/tax

1

11550


28.875




Dyn11

2

11275


28.188




3

11000

400

27.500




4

10725


26.813




5

10450


26.125




HV2 o'rash

LV o'rash

Nominal nisbat

Voltaj og'ish foizi

Ulanish belgisi

Joyga teging

Kuchlanishi

(V)

Kuchlanishi

(V)

AB% 2fab

Miloddan avvalgi / miloddan avvalgi

CA/tax

1

7150


17.875




Dyn11

2

6875


17.188




3

6600

400

16.500




4

6325


15.813




5

6050


15.125




3.2 O'rash qarshiligini tekshirish

Atrof-muhit harorati darajasi

O'rash

Joyga teging

O'lchangan qiymat (Ō)

Qarshilik nomutanosibligi foizi (foiz)

A-B

B-CC-A

H.V

1






2





3




4




5



L.V

a-b

b-c

c-a

Qarshilik nomutanosibligi foizi(foiz)






O'rash

Joyga teging

O'lchangan qiymat (Ō)



Qarshilik nomutanosibligi foizi (foiz)



A-B

B-CC-A

H.V.2

1






2




3




4




5



L.V

a-b

b-c

c-a

Qarshilik nomutanosibligi foizi(foiz)








3.3 Izolyatsiya qarshiligini o'lchash             

O'lchov sayti

Izolyatsiyaga qarshilik (MOh)







HV—LV TO YERGA

1000 dan katta yoki unga teng







LV—HV TO YERGA

1000 dan katta yoki unga teng







HV & LV TO YERGA

1000 dan katta yoki unga teng







3.4 AC quvvatga chidamli kuchlanish sinovi

Bosim ostidagi qismlar

Sinov kuchlanishi (kV)

Davomiyligi(s)

Natija





HV—LV TO YERGA


60

OʻTISH





LV—HV TO YERGA


60






 3.5 Yukning yo'qolishi va yuk oqimi yo'q

O'rtacha kuchlanish(kV)

RMS kuchlanish (kV)

Yuksiz oqim

Yuksiz yo'qotish (W)





(foiz)

O'lchangan qiymat







0.4

0.4







3.6 Induktsiya kuchlanish sinovi

Joyga teging

 

kuchlanishni qo'llash (kV)

Induksion kuchlanish(kV)

Induksion ko'p

Chastota (Hz)

Davomiyligi(s)

Natija


L.V

H.V







3








3.7 Empedans (foiz) va yukni yo'qotish testi

Atrof-muhit harorati darajasi

O'rash

Joyga teging

Tokni qo'llash ( A )

Sinov kuchlanishi (KV)

Qisqa tutashuv empedansi (foiz)

Yukni yo'qotish (W)

O'lchangan qiymatO'lchangan qiymat

 H.V-

L.V

3

10.5

0.4t=75 daraja I=Irt=75 daraja I=Ir
3.8 Plomba sinovi

Sinov usuli

Bosim qo'ying (kPa)

Qoldiq bosim (kPa)

Davomiyligi(h)

Natija




Havo bosimi




Oqish yo'q





Ikki kuchlanishli transformator simlari

200 kva 11kv 6.6kv 0.4kv dual voltage distribution transformer 7

TSS

1.Ikki kuchlanish transformatori nima

Ikki kuchlanishli taqsimlash transformatori bitta kirish kuchlanishidan bir nechta chiqish kuchlanish darajasini ta'minlay oladigan transformator turidir. Bunga transformator sariqlaridagi ikki yoki undan ortiq kuchlanishli kranlarni chiqish terminallariga ulash orqali erishiladi.

Ikki kuchlanishli transformatorning birlamchi sargisi odatda 15kV dan 33kV gacha bo'lgan yuqori kuchlanishli quvvat manbaiga ulanish uchun mo'ljallangan. Ikkilamchi o'rashda odatda 400V yoki 230V kuchlanish darajasida past kuchlanishli tarqatish tarmog'iga ulanishi mumkin bo'lgan bir nechta kranlar mavjud.

Ikki kuchlanishli transformatordan foydalanish tizim samaradorligi va xarajatlarni tejash nuqtai nazaridan sezilarli afzalliklarni berishi mumkin. Bir nechta kranli transformatordan foydalanib, turli xil iste'molchilarga ularning o'ziga xos ehtiyojlariga qarab turli xil kuchlanish darajalarini etkazib berish mumkin. Bu energiya isrofgarchiligini kamaytirish va umumiy tizim ish faoliyatini yaxshilashga yordam beradi.

Ikki kuchlanishli transformatordan foydalanishning yana bir afzalligi shundaki, u tarqatish tarmog'ida zarur bo'lgan transformatorlar sonini kamaytirishi mumkin. Bu tizimni sodda va tejamkorroq ishlashi mumkin.

An'anaviy energiya tarqatish tarmoqlarida foydalanishdan tashqari, ikki tomonlama kuchlanish transformatorlari qayta tiklanadigan energiya dasturlarida ham keng qo'llaniladi. Misol uchun, ular shamol fermalarida yoki quyosh elektr stantsiyalarida generatorlarning o'zgaruvchan chiqishini taqsimlash uchun mos bo'lgan barqaror kuchlanishga aylantirish uchun ishlatilishi mumkin.

Umuman olganda, er-xotin kuchlanishli tarqatish transformatori quvvatni taqsimlash ilovalari uchun moslashuvchan va samarali echimni ta'minlaydi, bitta kirish manbasidan bir nechta kuchlanish darajasini taklif qiladi, shu bilan birga tarmoqdagi qo'shimcha transformatorlarga bo'lgan ehtiyojni kamaytiradi.

2.200 kva transformatorning narxi qancha

3221 USD.00/SET

200 kva 11kv 6.6kv 0.4kv dual voltage distribution transformer 5

Issiq teglar: 200 kva 11kv 6,6kv 0,4kv ikki kuchlanishli taqsimlovchi transformator, Xitoy, etkazib beruvchilar, ishlab chiqaruvchilar, zavod, sotib olish, narx, sotuv

Sizga ham yoqishi mumkin

(0/10)

clearall